COMPACT Control System
Applies to COMPACT Unit & Top only
Electric Air Heater
The function is automatically activated when the TBLE air heater
is connected.
On a heating load, the power supplied to the air heater is con-
trolled in sequence with the heat exchanger.
Whenever the air velocity through the unit is low, the power
supplied is automatically reduced to prevent the electric heating
elements from becoming overheated. After the air heater has
been in operation, the supply air fan is always run for 3 minutes
more for cooling the air heater afterward. This occurs also if the
air handling uit has been manually switched off or automatic
functions have switched it off.
Air Heater for Hot Water
The function is automatically activated when the TBLE air heater
is connected.
On a heating load, the valve and actuator are controlled in se-
quence with the heat exchanger.
Pump Control
The circulation pump starts when there is a heating load and if
the outdoor temperature is low. Other times, the pump is exer-
cised at regular intervals.
Anti-frost Monitor
The air handling unit is stopped if freezing inside the air heater
is likely. The anti-frost function keeps the air heater warm at
13°C while the air handling unit is in operation and 25°C when
the unit is switched off.
Heating BOOST
From normal flow regulation, both the supply air and the ex-
tract airflows are increased to carry more heat into the
premises.
The fans are allowed to operate in the range between current
flow modes (low speed, high speed) and the preset max speed
flow.
The function only works if the air handling unit is operating in
the extract air regulation mode.
Intermittent Night-time Heating
The air handling unit is started and stopped within the preset
temperature limits for heating the premises when it is normally
stopped by the time switch clock (timer).
Intermittent night-time heating requires an external room
sensor, and that the air handling unit is connected to an air
heater for reheating.
When the function is activated, the air handling unit detects
when the room temperature drops below the preset start tem-
perature. The unit starts with preset flows and the supply air
temperature setpoint.
Morning BOOST
The air handling unit starts at the preset time, before the start
time of the time switch clock, with preset temperature setpoint
for heating the room.
Applies to COMPACT Unit & Top only
Preheating the Outdoor Air
Preheating the outdoor air if the outdoor temperature is cold
and the humidity is high can prevent condensation from form-
ing in the air handling unit’s filters. Preheating may also be nec-
essary to heat the air if during a spell of extremely cold weather.
The outdoor air preheating function requires placing the air
heater in the outdoor air duct and the TBLZ-1-53-a (controlling
the air heater preheating function).
The TBVL valve set can be used for the air heater for hot water
and if a pump is required, the TBPA pump set can be used.
The following types of air heater can be selected:
• Electric air heater of pause/pulse type
• Electric air heater, 0–10 V.
• Air heater for hot water with anti-frost monitor function.
• Air heater for hot water without anti-frost monitor function.
Control Function
Temperature sensors in the ducts keep the preset temperature
constant. The setpoint required can be set in the hand-held
micro terminal.
Anti-frost Monitor Function
The alarm limit and heat keeping function settings are common
for the preheating coil and the ordinary air heater in the supply
air path.
Pump Control
Provision is available for controlling pump operation. The set-
tings for exercising will then be common with the ordinary air
heater in the supply air ductwork.
Electric Air Heater
Overheat monitor and recooling whenever the air handling unit
stops.
Heating